Caterpillar G3520-2000 Gas Generator Set
CAT G3520-2000 Gas Generator Set is a 97.6 L iter Displacement Engine with 170 mm Bore and 215 mm Stroke.
Equipped with Dual ADEM™ A4 Electronic Control Unit (ECU) LH with Electronic Unit Injector Fuel System Rigid Wiring Harness and ADEM™ A5 Governor.The Prime Power for 60 Hz Generator Set (1800 RPM) of G3520-2000 Gas Generator Set is 2500 kVA (2000 kW).
G3520-2000 Gas Generator Set Powered by CAT Diesel Engine with EMCP 4 Control Panel, Diesel Genset with Turbocharged-Aftercooled.
CAT Diesel Generator Sets Meet Tier III/Tier IV Emission Standards. As Part of EMAC, CAT Diesel Generator Sets Also Provide 50 Hz and 60 Hz Diesel Generator Sets. Engine Brands Include Cummins, Deutz, Perkins, MTU, WeiChai and CAT.
Our Diesel Generator Set Series Includes High Power Medium and High Voltage Generator Sets and High Power Low Voltage Generator Sets. The Engine Provides Electronically Controlled and Mechanical Fuel Injection Systems for Customers to Choose. In Addition to Generating Diesel Generator Sets, We Can Also Supply Marine Diesel, Oil, Gas, Marine Generator Sets.
We Provide Full Life Cycle Services for All Customers, From Design to Power System Supply, From Installation to Commissioning, From After-Sales Service Training to Spare Parts Supply, From Troubleshooting to Overhaul Technical Support.
Advantages of Caterpillar G3520-2000 Gas GenSet
-
It is synchronized with Cummins’ advanced design and sophisticated manufacturing, adapts to harsh working conditions, and has high-intensity and heavy-duty work capabilities
-
The Holset wastegate valve makes the low speed performance more perfect and the power performance better.
-
The cylinder block and cylinder head adopt integrated design to prevent the occurrence of engine water and oil leakage. The parts are 40% less than other similar engines, and the failure rate is greatly reduced.
-
Using forged steel camshaft and crankshaft, high-strength cylinder design, many parts are cast on the cylinder, with high rigidity, high pressure resistance, good reliability and longer service life.
-
The cylinder liner adopts a platform mesh honing design, which effectively prevents oil leakage with a perfect geometric structure, and adopts advanced technology such as new piston ring components and gasket crimping molding to reduce oil loss.
-
Holset supercharger with integrated wastegate valve, low speed response and strong power.
Technical Specifications
Basic Introduction of CAT G3520-2000 Gas Generator Set
Engine Model: | G3520-2000 |
Engine Type: | N/A |
Displacement: | 97.6 L |
Rated Speed: | 1800 RPM |
Aspiration Method: | Turbocharged |
Emission Standard: | N/A |
Bore*Storke: | 170 mm * 215 mm |
Packing Size(L*W*H): | 8534 mm * 2386 mm * 6736 mm |
Wet Weight: | 22000 Kg |
Lead Time: | 15-30 Working Days |
Payment Terms: | T/T ,L/C |
Engine Model |
Continuous Power |
Aspiration |
Fuel System |
G3520H-2000 | 2000 ekw / 2500 KVA | Turbocharged | Electronic Fuel Control Valve |
G3520H-2500 | 2500 ekw / 3125 KVA | Turbocharged | Electronic Fuel Control Valve |
——END—— |
General Information of CAT G3520H-2000 Gas Generator Sets |
|||
Engine Model | G3520-2000 | Continuous Power | 2000 ekW |
Bore | 170 mm / 6.7 in | Stroke | 215 mm / 8.5 in |
Aspiration | Turbocharged | Fuel System | Electronic Fuel Control Valve |
Governor Type | ADEM™ A4 | Emissions Performance | U.S. EPA Stationary Certified |
Displacement | 97.6 L / 5956 in³ | Compression Ratio | 11.5:1 |
Length | 8534 mm / 336 in | Width | 2386 mm / 94 in |
Height | 3230 mm / 128 in | Dry Weight | 24800 kg / 54675 lb |
——END—— |
Package Performance of CAT G3520H-2000 Gas Generator Sets |
|||
Continuous | Continuous | ||
Performance | Frequency | 60 Hz | 60 Hz |
Genset power rating @ 0.8 power factor – ekW (kVA) | 2000 | 2500 | |
Emissions | Certified – U.S. EPA Stationary | Certified – U.S. EPA Stationary | |
Performance number | EM4305 | EM4305 | |
Fuel Consumption | 100% Load with Fan – MJ/ekW-hr (Btu/ekW-hr) | 9.61 | 9116 |
75% Load with Fan – MJ/ekW-hr (Btu/ekW-hr) | 9.98 | 9465 | |
50% Load with Fan – MJ/ekW-hr (Btu/ekW-hr) | 10.92 | 10357 | |
Cooling System | Radiator air flow restriction – kPa (in. water) | 0.12 | 0.5 |
Radiator air flow – m3 /min (cfm) | 1814 | 64060 | |
Radiator ambient capability @ 304 m (1000 ft) – °C (°F) | 35 | 100 | |
Auxiliary circuit temperature (maximum inlet) – °C (°F) | 54 | 130 | |
Jacket water temperature (maximum outlet) – °C (°F) | 99 | 210 | |
Inlet Air | Combustion air inlet flow rate – Nm3/bkW-hr (ft3/min) | 4.32 | 6110 |
Altitude Capability | At 25°C (77°F) ambient, above sea level – m (ft) | 2690 | 8825 |
Exhaust System | Exhaust temperature – engine outlet – °C (°F) | 472 | 881 |
Exhaust Gas Flow – Nm3/bkW-hr (ft3/min) | 4.58 | 16407 | |
Exhaust Gas Mass Flow – kg/bkW-hr (lb/hr) | 5.78 | 28033 | |
Exhaust System | Heat Rejection To Jacket Water – kW (Btu/min) | 602 | 34212 |
Heat Rejection To Exhaust (Lhv To 120°C/248°F) – kW (Btu/min) | 1392 | 79154 | |
Heat Rejection To Auxiliary Circuit – kW (Btu/min) | 224 | 12763 | |
Heat Rejection To Atmosphere From Engine And Generator – kW (Btu/min) | 265 | 15092 | |
Heat rejection to jacket water circuit (JW+AC1+OC) – kW (Btu/min) | 1035 | 58839 | |
——END—— |
Optional Equipment of CAT G3520H-2000 Diesel Generator Sets |
|||||
Type | 1. Bus Bar | Generators | Output Voltage | Engine | Air Cleaner (Single Element) |
2. Circuit Breaker | 1. 380 V | 1. Installed | |||
3. 400 A | 2. 440 V | 2. Supplied Loose | |||
4. 800 A | 3. 480 V | Muffler | |||
5. 1200 A | 4. 600 V | 1. Industrial Grade (15 Db) | |||
6. 1600 A | 5. 2400 V | 2. Residential Grade (18 Db) | |||
7. 2000 A | 6. 2400 V | 3. Critical Grade (25 Db) | |||
8. 2500 A | 7. 4160 V | 4. Spark Arresting | |||
9. 3200 A | 8. 12470 V | Starting | |||
10. 4000 A | 9. 13200 V | 1. Standard Batteries | |||
11. Ul | 10. 13800 V | 2. Standard Electric Starter(S) | |||
12. Iec | Temperature Rise (Over 40°C) | 3. Air Starter(S) | |||
13. 3-Pole | 1. 150°C | 4. Jacket Water Heater | |||
14. 4-Pole | 2. 105°C | 5. N/A | |||
15. Manually Operated | 3. 125°C/130°C | 6. N/A | |||
15. Electrically Operated | 4. 80°C | ||||
Attachments | 1. Cold Weather Bundle | Terms | 1. 2 Year | Coverage | 1. Silver |
2. Dc Lighting Package | 2. 3 Year | 2. Gold | |||
3. Ac Lighting Package | 3. 5 Year | 3. Platinum | |||
4. Motorized Louvers | 4. 10 Year | 4. Platinum Plus | |||
Certifications | 1. Ul 2200 Listed | Controller | 1. EMCP 4.3 | Winding type | 1. Random Woun |
2. Csa Certified | 2. EMCP 4.4 | 2. Form Wound | |||
Attachments | 1. Local Annunciator Module | Ancillary Equipment | 1. Automatic Transfer Switch (Ats) | Vibration Isolators | 1. Rubber |
2. Remote Annunciator Module | 2. Uninterruptible Power Supply (Ups) | 2. Spring | |||
3. Load Share Module | 3. Paralleling Switchgear | 3. Seismic Rated | |||
4. Remote Monitoring Software | 4. Paralleling Controls | 4. N/A | |||
Radiator | 1. Factory Provided (2 Mw Only) | Enclosure | 1. Weather Protective | Fuel System Pressure | 1. Standard |
2. Dealer / Customer Provided | 2. Sound Attenuated | 2. Low | |||
Trip Unit | 1. LSI | Charging | 1. Battery Charger – 20A | Radiator | 1. Factory Provided (2 Mw Only) |
2. LSI-G | 2. Battery Charger – 35A | 2. Dealer / Customer Provided | |||
3. LSIG-P | 3. Battery Charger – 50A | 3. N/A | |||
Excitation | 1. Permanent Magnet (Pm) | Connectivity | 1. Ethernet | Attachments | 1. Anti-Condensation Heater |
2. N/ A | 2. N/A | 2. Stator And Bearing Temperature Monitoring And Protection | |||
——END—— |
Standard Features of CAT G3520H-2000 Diesel Generator Sets |
|||
Cat Natural Gas Engine | 1. Designed For Maximum Performance On Lowpressure Gaseous Fuel Supply | Generators | 1. Superior Motor Starting Capability Minimizesneed For Oversizing Generator |
2. Robust 20 Cylinder High Speed Block Design Provides Prolonged Life And Lower Owning And Operating Costs | 2. Designed To Match Performance And Output Characteristics Of Cat Engines | ||
3.Certified U.S. Epa Stationary Non-Emergency Standards, To Be Used In Emergency And NonEmergency Applications | |||
Financing | 1. Contact Your Local Cat Dealer For Availability In Your Region | EMCP 4 Control Panels | 1. User-Friendly Interface And Navigation |
2. Options Include Loans, Finance Lease,Operating Lease, Working Capital, And Revolving Line Of Credit | 2. Scalable System To Meet A Wide Range Ofinstallation Requirements | ||
3.Caterpillar Offers An Array Of Financial Products To Help You Succeed Through Financial Service excel3lencen | 3. Expansion Modules And Site Specific Programming For Specific Customer Requirements | ||
Cooling System | 1. Optional Radiator Available To Operate In Ambient Temperatures Up To 43°C (110°F) | Worldwide Product Support | 1. Cat Dealers Have Over 1,800 Dealer Branch Stores Operating In 200 Countries |
2. Package Tested To Ensure Proper Cooling Of Complete Generator Set | 2. Your Local Cat Dealer Provides Extensivepost-Sale Support, Including Maintenance And Repair Agreements | ||
Generator Set Package | 1.Accepts 100% Block Load In One Step | ||
2. Conforms To Iso 8528-5 G2 Load Acceptance Criteria | |||
3. Facilitates Compliance With Nfpa 110, Type 10 Starting And Loading Requirements (Lv) | |||
4. Reliability Verified Through Torsional Vibration, Fuel Consumption, Oil Consumption, Transient Performance, And Endurance Testing | |||
——END—— |